Signal Converter

TECHNICAL DATA

Inputs
Resistance Bulb Thermometer (PT100) 2 or 3 wire, Span as requested.
Min Span: 10°C
Max Span: 600°C
Slidewire & Potentiometer Span as requested.
Minimum: 50 R
Maximum: 5K0 R
Variable Resistance Span as requested.
Min Span: 50 R
Max Span: 500 R
Voltage Span as requested.
Min Span: 4mV
Max Span: 250V
Input resistance > 1M0 R
Current Span as requested.
Max Span: 100mA
0-lmA into 1K0 R
1-5mA into 240 R
0-10mA into 100 R
0-20mA into 51 R
4-20mA into 62 R
10-50mA into 24 R
   
Output
Current Span as requested. Min Span: lmA Max Span: 20mA Compliance 20V
Voltage Span as requested. Min Span: 1mV Max Span: 20V Into 500 R minimum.
   
Other
Load Stability 0.02%.
Ripple 0.3% (peak)
Response Time < 250ms to 99%
Linearity Proportional to input +/ 0.05% of full scale.
Temp Coefficient +/- 0.01/ per°C.
Operating Temp 0 to +60°C
Storage Temp - 20 to + 65°C.
Mains Supply 100-120V 210-250V 50/60Hz. Fused Internally, isolated from both I/P and Relay Contacts.
DC Supply 24V DC Fused Internally, isolated from both I/P and Relay Contacts.
Power Consumption 3VA Max.
Housing 75 x 55 x 110mm Grey Makrolon Case suitable for Surface or DIN Rail mounting.
Cable Entry The connections are by top mounted screw terminals which will accept wires up to a maximum of 2.5mm diameter.

OVERVIEW

Function General purpose Non-isolating DC Signal Converter. Accepts Input Signals from Resistance Bulb Thermometer (PT100), Resistance, Voltage and Current Sources. The Output can be either Current or Voltage, the unit can also be used to boost or invert signals.

Electroserv (TC & S) Ltd, PO BOX 163, 6 Short Street, Macclesfield, Cheshire, England UK, SK11 8GA
designed by focus systems ltd © 2007