West P8170 1/8 Din Valve Motor Controller
TECHNICAL DATA
| Features | |
| Control Types | Full PID with Pre-tune, Self-tune and manual tuning modes. |
| Valve Control | Open Loop Valve Motor Drive. |
| Auto/Manual | Selectable from front panel or via digital input, with bumpless transfer. |
| Output Configuration | Up to 5 possible, two required for valve control, additional outputs for alarm, 24VDC transmitter power supply or retransmit of process value or setpoint. |
| Alarm 1 & 2 Types | Process high, process low, SP deviation, band, logical OR / AND. Also 1 loop alarm for process control security. Process alarms have adjustable hysteresis. |
| Human Interface | 4 button operation, dual 4 digit 10mm & 8mm high LED displays, optional choice of colours (Red/Red, Red/Green, Green/Red or Green/Green), plus 5 LED indicators |
| PC Configuration | Off-line configuration from PC serial port to dedicated configuration socket (communications option not required). Configuration Software for Windows 98 or higher. West Part Number:PS1-CON |
| Input | |
| Thermocouple | J, K, C, R, S, T, B, L, N & PtRh20%vsPtRh40%. |
| RTD | 3 Wire PT100, 50 Ohm per lead maximum (balanced) |
| DC Linear | 0 to 20mA, 4 to 20mA, 0 to 50mV, 10 to 50mV, 0 to 5V, 1 to 5V, 0 to 10V, 2 to 10V. Scaleable -1999 to 9999, with adjustable decimal point |
| Impedance | >10M Ohm for Thermocouple and mV ranges, 47K Ohm for V ranges and 5 Ohm for mA ranges |
| Accuracy | ±0.1% of input range ±1 LSD (T/C CJC better than 1°C) |
| Sampling | 4 per second, 14 bit resolution approximately |
| Sensor Break Detection | < 2 seconds (except zero based DC ranges), control O/P's turn off, high alarms activate for T/C and mV ranges, low alarms activate for RTD, mA or V ranges |
| Output and Options | |
| Control & Alarm Relays | Contacts SPDT 2 Amp resistive at 240V AC (120V AC Max for direct VMD), >500,000 operations. (1A 2xSPST 200,000 operations for Dual Relay) |
| Control SSR Driver Outputs | Drive capability >10V DC in 500 Ohm minimum |
| Triac Outputs | 0.01 to 1 Amp AC, 20 to 280Vrms, 47 to 63Hz, 140V Max for direct VMD |
| DC Linear Outputs | 0 to 20mA, 4 to 20mA into 500 Ohm max, 0 to 10V, 2 to 10V, 0 to 5V into 500 Ohm min. Accuracy ±0.25% at 250 Ohm (degrades linearly to 0.5% for increasing burden to specified limits) Retransmit of PV or SP Only. |
| Transmitter Power Supply | Output 24VDC (nominal) into 910 Ohm minimum to power external devices |
| Serial Communications | 2 Wire RS485, 1200 to 19200 Baud, Modbus protocol |
| Digital Input | Selects between 2 setpoints or Auto/Manual control. Volt free or TTL input |
| Remote Setpoint/Valve Position Auxiliary Input | 0 to 20mA, 4 to 20mA, 0 to 100mV, 0 to 5V, 1 to 5V, 0 to 10V, 2 to 10V or =2K Ohm Potentiometer Scaleable -1999 to 9999. For Valve Position Indication or Remote Setpoint Input. Local/Remote setpoint selected from digital input (supplied as part of Full Auxiliary) or front panel. |
| Operating and Environmental | |
| Temperature & RH | 0 to 55°C (-20 to 80°C storage), 20% to 95% RH non-condensing |
| Power Supply | 100 to 240V 50/60Hz 7.5VA (optional 20 to 48V AC 7.5VA/22 to 65V DC 5 watts) |
| Front Panel Protection | IEC IP66 (Behind panel protection is IP20) |
| Approvals and Certification | CE, UL & ULC recognised |
DIMENSIONS
CONNECTION DETAILS
FIELD RECONFIGURATION
InputORDER CODE
MAIN FEATURES
OVERVIEW
The new Plus Series VMD Controllers have been specifically designed for open loop valve motor drive applications and feature the improved Plus Series interface and greater field flexibility.