West 6600 1/16 DIN Plastics Controller
TECHNICAL DATA
| Features | |
| Control Types | Full PID with Pre-tune, Self-tune, Manual Tuning, or On-Off control. Heat only or heat & cool |
| Soft Start | Allows lower SP value and cycle time during the process start-up phase |
| Auto/Manual | Selectable from front panel, with bumpless transfer. Instant power-off feature also available as standard |
| Output Configuration | Up to 4 total. Max 2 for control (Heat & Cool), max 3 for Alarms, max 1 for retransmit Process value or Setpoint |
| Process Alarm Types | Process high, process low, SP deviation, band, logical OR |
| Heater Break Alarm Types | Current low or high, (in absolute amps or % of nominal current) plus contactor/thyristor short circuit |
| Human Interface | 4 button operation, dual 4 digit 10mm & 8mm high LED displays, plus 3 LED indicators for alarms, tuning and set-up |
| PC Configuration | Off-line configuration from serial port if RS485 option is fitted. |
| Input | |
| Thermocouple | J, K, R, S, T, B, L, & N. |
| RTD | 3 Wire PT100, 50 Ohm per lead maximum (balanced) |
| Impedance | >100M Ohm |
| Accuracy | +/- 0.25% of input span +/- 1 LSD (T/C CJC better than 0.7°C) |
| Sampling | 4 per second, 14 bit resolution approximately |
| Sensor Break Detection | < 2 secs, control O/P's turn off, high alarms activate for thermocouple ranges, low alarms activate for RTD |
| Heater Current | 0-50mA secondary from external current transformer. Display is scaleable up to 100 amps |
| Output and Options | |
| Control & Alarm Relays | Contacts *SPDT 2Amp resistive at 240V AC,>500,000 operations. (Dual relay=SPST for O/P's 2 & 4) |
| Control SSR Driver Outputs | Drive capability, output 1>10V DC into 500 Ohm min, output 2>4.2V DC into 250 Ohm min |
| Solid State (Triac) Outputs | 0.01 to 1 Amp AC 20 to 280V, 47 to 63Hz |
| Retransmit Outputs | 0-20/4-20mA into 500 Ohm max, 0-10/0-5V into 500 Ohm min. Accuracy typically +/- 0.25% |
| Communications | 2 Wire RS485, 1200 to 9600 Baud, Modbus or West ASCII (Selectable) |
| Dual SP/Current Transfer | Volt free or TTL input. Selects between 2 setpoints or quick transfer of heater current as nominal value |
| Operating and Environmental | |
| Temperature & RH | 0 to 55°C (-20 to 80°C storage), 20% to 95%RH non-condensing |
| Power Supply | 100 to 240V 50/60Hz 7.5VA (optional 20 to 50V AC 7.5VA/22 to 65V DC 4W) |
| Front Panel Protection | IEC IP66 (Behind panel protection is IP20) |
| Approvals and Certification | CE, UL & ULc |
DIMENSIONS
CONNECTION DETAILS
FIELD RECONFIGURATION
InputORDER CODE
MAIN FEATURES
OVERVIEW
The West 6600 provides high quality control in applications requiring a heater break function or soft-start for process warm up. Heater current can also be displayed, removing the need for a separate ammeter.