West 6400 1/16 DIN Profiler Controller
TECHNICAL DATA
| Features | |
| Control Types | PID with Pre-tune and RaPID fuzzy logic, or Manual Tuning. Heat or Heat/Cool, applications |
| Auto/Manual | Selectable from front panel, with bumpless transfer |
| Output Configuration | Up to 3 total. Max 2 for control (Heat & Cool), max 2 for Alarms, max 1 for retransmit PV or SP |
| Alarm 1 & 2 Types | Process high, process low, setpoint deviation and band |
| Human Interface | 4 buttons, 10mm & 8mm high LED's, plus run-hold, tune, event & profile/control status LED's |
| PC Configuration | Off-line configuration & profile editing via config socket (comms option not required) |
| Profiles | |
| Number of Programs | 4, each with 16 free-form segments (Ramp/Dwell/End). Max segment length 99 hours 59 minutes |
| Delayed Start | Max 99 hours 59mins delay from initiation to program start |
| Guaranteed Soak | Holds program if PV is outside of specified hold band during dwell segments |
| Program Cycles | 1 to 9999 or infinite (continuously re-starts program at end) |
| Ramp Rate Definition | Either ramp rate, or time to final setpoint |
| Power Loss Recovery | Hot (continue profile from point of power fail) or Cold (end profile and return to controller mode) |
| Input | |
| Thermocouple | J, K, R, S, T, B, L, & N. |
| RTD | 3 Wire PT100, 50 Ohm per lead maximum (balanced) |
| DC Linear | 0-20/4-20mA, 0-50/10-50mV, 0-5/1-5/0-10/2-10V. Scaleable -1999 to 9999, dec point available |
| Impedance | >100M Ohm for Thermocouple and mV ranges, 47K Ohm for V ranges and 4.7 Ohm for mA ranges |
| Accuracy | +/- 0.25% of input span +/- 1 LSD (T/C CJC better than 0.7°C) |
| Sampling | 4 per second, 14 bit resolution approximately |
| Sensor Break Detection | < 2 secs (except zero based DC ranges), control O/P's turn off, *high alarms activate (*low for RTD inputs) |
| Output and Options | |
| Control/Alarm/Event Relay | Contacts SPDT 2Amp resistive at 240V AC, >500,000 operations |
| DC for SSR | Drive capability >4.2V DC in 1K Ohm minimum (10V 500 Ohm version available) |
| DC Control/Retransmit | 0-20/4-20mA into 500 Ohm max, 0-10/0-5V into 500 Ohm min. Accuracy, Control OP +/- 0.5%, Retransmit +/- 0.25% |
| Solid State (Triac) | 0.01 to 1 Amp AC 20 to 280V, 47 to 63Hz |
| Remote Run-Hold | Volt free or TTL input (Hold = -0.6 to 0.8V or contact open, Run = 2 to 24V or contact close) |
| Communications | 2 Wire RS485, 1200 to 9600 Baud, Modbus protoc |
| Operating and Environmental | |
| Temperature & RH | 0 to 55°C (-20 to 80°C storage), 20% to 95% RH non-condensing |
| Power Supply | 100 to 240V 50/60Hz 7.5VA (optional 20 to 50V AC 7.5VA/22 to 65V DC 4W) |
| Front Panel Protection | IEC IP66 (Behind panel protection is IP20) |
| Approvals and Certification | CE, UL & Ulc |
DIMENSIONS
CONNECTION DETAILS
FIELD RECONFIGURATION
InputORDER CODE
MAIN FEATURES
OVERVIEW
The West 6400+ is a programmable safety cut out with optional outputs for annunciators and alarms. A latched relay cuts power to your process if safe values are exceeded. The unit must be reset before the process can continue. It has the improved Plus Series hardware and user interface for optimal ease of use.